The FZK 011 mechanical thermostat is used for controlling heating and cooling equipment, filter fans or signal devices where a higher degree of sensing accuracy is required. An integrated resistor (RF) can be connected to improve the switch temperature difference (see Option note). The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact.
Technical Data
Switch difference approx. 9 °F (5 K), tolerance -5.4/+3.6 °F (-3/+2 K)1 Sensor element thermostatic bimetal Contact type SPDT / change-over contact Service life >100,000 cycles Min. switching capacity 10mA Max. switching capacity, NC 10 A resistive / 4 A inductive @ AC 120 V
10 A resistive / 4 A inductive @ AC 250 V
DC 30 WMax. switching capacity, NO 5 A resistive / 2 A inductive @ AC 120 V
5 A resistive / 2 A inductive @ AC 250 V
DC 30WEMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 Connection 4-pole terminal, clamping torque 0.5Nm max., rigid wire 2.5mm²stranded wire(with wire end ferrule) 1.5mm² Mounting clip for 35mm DIN rail, EN50022 Casing plastic according to UL94 V-0, light grey Dimensions 67 x 50 x 38mm Fitting position variable Operating/Storage temperature -4 to +176 °F (-20 to +80 °C) / -49 to +176 °F (-45 to +80 °C) Protection type IP20 Weight approx. 10g Approvals UL File No. E164120 ¹ If the Normally Closed contact is used, the switch temperature difference could be reduced by connecting terminal “N” (RF heating resistor). It causes the thermal feedback which is subject to surrounding conditions and thus has to be determined for
each individual application.² When connecting with stranded wires, wire end ferrules must be used.
3 Voltage only needs to be specified if the optional use of the RF resistor is desired.
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.
Art. No. Operating voltage Setting range 01170.0-00 230VAC +5 to +60 °C 01170.0-01 230VAC +40 to +140 °F 01170.0-02 230VAC -20 to +30 °C 01170.9-00 120VAC +40 to +140 °F 01170.9-01 120VAC +5 to +60 °C - [download id=”148″ format=”1″]